FAULT CODES 2
None
Fault code
Cause
Action
(click on appropriate action
)
E3
Fault in safety chain
Check the temperature limiter and connecting cables
E5
Internal fault
Check the ionisation electrode and connecting cables
F0
Internal fault
Control unit
F1
Max. flue gas temperature exceeded
Check heating system fill level, circulation pump & system
F2
Temperature limiter has responded
Check system fill level, pump & system. temperature limiter
F3
Flame signal is present at burner start
Check ionisation electrode and connecting cable
F4
No flame signal detected
Check ignition operation
F8
Fuel valve closes too late
Check gas train, check both control paths
F9
Fan speed too low during burner start
Check fan, cables and power supply to fan; check fan control
FA
Fan idle state not reached
Check fan, cables and power supply to fan; check fan control
FC
Electrical fan control (control unit) faulty
Check fan connecting cable, control unit
Fd
Fault, burner control unit
Check ignition electrodes, cables, interference (EMC) field
FF
Fault, burner control unit
Check ignition electrodes, cables, interference (EMC) field