Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach U-gauge to gas inlet pressure test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
If required, reset boiler.
Allow self-check to complete and ignition sequence to commence.
Inlet pressure should remain above N.G.10 mb, L.P.G. 25 mb throughout the ignition sequence (see note 2.).
Allow self-check to complete and ignition sequence to commence.
Inlet pressure should remain above N.G.10 mb, L.P.G. 25 mb throughout the ignition sequence (see note 2.).