Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to AC Volts Set meter to measure AC Volts
Gain access to PCB (use Insulation Mat as required)
Boiler ON/OFF switch set to ON position
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Test 1. Measure for A/C voltage across the mains input terminals of the On/Off switch, blue & brown leads with plastic insulation.
Expected voltage, mains voltage, if voltage not as expected choose "Test 1. voltage not as expected - mains input" from below.
Test 2. Measure for A/C voltage across the mains output terminals of the On/Off switch, blue & brown leads with no plastic insulation.
Expected voltage, mains voltage