Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
If fitted, disconnect timer/programmer or receiver from connector X5 & make safe (see note)
No demands
No demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
With X5 disconnected, does the pump still
run continuously and / or boiler attempt to
fire after self-check has completed?
run continuously and / or boiler attempt to
fire after self-check has completed?
Isolate as per TOPs P4
and refit as necessary