Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove 1 connector from overheat stat and make safe
Remove fan control connector from fan assembly and make safe
Remove fan control connector from fan assembly and make safe
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure for DC voltage across pin 13 connector X20 and a suitable earth connection.
Expected voltage approximately 8.0 Vdc or greater.
Note.
Reset appliance as required until test complete.
Expected voltage approximately 8.0 Vdc or greater.
Note.
Reset appliance as required until test complete.

Isolate as per TOPs P4
and refit as necessary