Set Appliance State:

Turn Hot Water Tap On
Set flow rate to 3 l/min
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Enter the installer mode and access level A - b2.
(click here for information on how to do this)
The DHW flow rate should be displayed.
Is the boiler showing the correct DHW flow rate?
Notes:
1. The flow rate displayed may differ slightly from that set due to the lack of accuracy when using a weir cup, use engineering discretion to ascertain if approximately the correct flow rate is being displayed.
2. The display updates slowly so allow for this delay if altering the flow rate.