Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to AC Volts Set meter to measure AC Volts
Turn Hot Water Tap On
Gain access to PCB (use Insulation Mat as required)
Remove the connector from the fan assembly and make safe
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow boiler self-check to complete.
Reset appliance as necessary (hold down both arrow buttons until display changes).
Measure the AC voltage between each of the pins listed below and pin 3 (purple), the voltages measured should be approximately as listed in the table.
PinVoltage
4 (Brown)240V AC
5 (White)36V AC
6 (Orange)36V AC
7 (Yellow)36V AC

Are the voltages measured as expected?