Set Appliance State:
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
CH temperature set to MAX
Allow the boiler to run on central heating, is the heating operating satisfactorily?
Monitor the pressure to check that it does not rise excessively as the system heats.
Note:
Syphon fill mode can be disabled if required to test the heating by entering the service/installer settings (press and hold radiator and tap buttons simultaneously for 3 seconds) then select "special function" > "siphon fill prog" > "Off" - this should only be done during a repair or maintenance visit and must be reset correctly afterwards.
Allow the boiler to run on central heating, is the heating operating satisfactorily?
Monitor the pressure to check that it does not rise excessively as the system heats.
Note:
Syphon fill mode can be disabled if required to test the heating by entering the service/installer settings (press and hold radiator and tap buttons simultaneously for 3 seconds) then select "special function" > "siphon fill prog" > "Off" - this should only be done during a repair or maintenance visit and must be reset correctly afterwards.