Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature probe to pipe as indicated by the red arrow
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Set boiler temperature control for CH to MAX.
Run the appliance and allow the system to heat.
The boiler should in CH mode until it reaches maximum temperature of approximately 88°C, it should then modulate down or shut down without an overheat or circulation error occurring - this is correct operation.
Does the boiler operate correctly?
Note:
To speed up the process the heating load can be reduced by turning off some radiators. If overheat occurs isolate appliance immediately.
Run the appliance and allow the system to heat.
The boiler should in CH mode until it reaches maximum temperature of approximately 88°C, it should then modulate down or shut down without an overheat or circulation error occurring - this is correct operation.
Does the boiler operate correctly?
Note:
To speed up the process the heating load can be reduced by turning off some radiators. If overheat occurs isolate appliance immediately.