Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Attach pressure gauge to fan pressure test point
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Reset appliance as necessary and allow the boiler to complete its self-check.
Run the appliance in service mode (hold down the ok button until sweep mode activates).
Operate the boiler at maximum rate.
Check the observed fan pressure against the table.
Note:
To turn service mode off press the back button then ok to confirm.