Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Flow rate at hot tap of 8 litres/min
Attach temperature clamps to flow pipe just below the primary sensor
and the return pipe just above the pump nut as indicated by the red arrows
Boiler DHW thermostat set to MAX
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the burner to ignite and the boiler to run in DHW mode for at least 2 minutes.
Measure the temperature differential between the flow and return pipes.
Expect a differential of approximately 11°C or less.
Is the differential as expected?
Note:
Ensure a good contact is made with the temperature clamps