Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove connector CN2 from the main PCB
Remove the AC fan connector (3 wire) from the fan
Remove the AC fan connector (3 wire) from the fan
Measurement:
Test 1:
Measure the resistance between pin 5 (brown) on CN2 and the brown on the fan connector.
Expect continuity.
Test 2:
Measure the resistance between pin 4 (blue) on CN2 and the blue on the fan connector.
Expect continuity.
Test 3:
Measure the resistance between earth on the fan connector and the boiler chassis.
Also inspect the condition of the harness visually checking for any damaged insulation.
Measure the resistance between pin 5 (brown) on CN2 and the brown on the fan connector.
Expect continuity.
Test 2:
Measure the resistance between pin 4 (blue) on CN2 and the blue on the fan connector.
Expect continuity.
Test 3:
Measure the resistance between earth on the fan connector and the boiler chassis.
Also inspect the condition of the harness visually checking for any damaged insulation.

Isolate as per TOPs P4
and refit as necessary