Set Appliance State:

Mains Power Off
CH Demand
Boiler CH thermostat set to MAX
Attach temperature probes as per the red arrows
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow the appliance to fire in central heating mode and heat until maximum temperature is reached.
Monitor the appliance temperature and observe the display.
Note:
1. Do not rely on the boilers temperature reading.
2. It may be advisable to turn off some radiators to speed up this test.
Please select from the options below:
BOILER OVERHEATS BEFORE 90°C IS REACHED
BOILER CONTINUES TO HEAT BEYOND 90°C