Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Gain access to interface PCB
Remove connector CN7 from the interface PCB and make safe.
NO demands
Remove connector CN7 from the interface PCB and make safe.
NO demands
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Wait until the fan has stopped after start up sequence.
Test 1: Measure the AC voltage between the top left hand Pin of connector CN7 and a suitable earth. Expect approximately 1.1 VAC
Test 2: Apply a central heating demand.
Measure the AC voltage between the top left hand Pin of connector CN7 and a suitable earth. Expect an increase in voltage of approximately 0.05 VAC or greater from the first voltage measured.
Note: It does not matter if the appliance is displaying a fault code for this test.
Test 1: Measure the AC voltage between the top left hand Pin of connector CN7 and a suitable earth. Expect approximately 1.1 VAC
Test 2: Apply a central heating demand.
Measure the AC voltage between the top left hand Pin of connector CN7 and a suitable earth. Expect an increase in voltage of approximately 0.05 VAC or greater from the first voltage measured.
Note: It does not matter if the appliance is displaying a fault code for this test.

Isolate as per TOPs P4
and refit as necessary