Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Boiler DHW setting to MAX
Refit diverter valve motor
Refit diverter valve motor
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Observation:
Allow boiler to ignite and run on DHW
With a flow rate at the tap of approximately 9.9 litres/min is there a temperature rise of approximately 40° C and is operation satisfactory?
Note:
Flow rates less than stated above will produce a greater temperature rise.
With a flow rate at the tap of approximately 9.9 litres/min is there a temperature rise of approximately 40° C and is operation satisfactory?
Note:
Flow rates less than stated above will produce a greater temperature rise.