Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach pressure gauge to the inlet pressure test point
Gas On
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Observation:
Measure the gas inlet pressure does it remain constant and above a minimum of 17mb?
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Isolate as per TOPs P4
and refit as necessary