Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Gain access inner combustion chamber
Fit APS test kit to left hand connection on APS (tube that runs to venturi)
Ensure pressure reads zero before turning power on
Fit APS test kit to left hand connection on APS (tube that runs to venturi)
Ensure pressure reads zero before turning power on
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Once fan has started to run increase the pressure via
the APS testing kit to approximately 2mbar.
Can sparking now be seen at the electrode?
Note:
Syringe will only need to be pushed in slightly to
reach 2mb, take care not to overpressurise.
the APS testing kit to approximately 2mbar.
Can sparking now be seen at the electrode?
Note:
Syringe will only need to be pushed in slightly to
reach 2mb, take care not to overpressurise.