Set Appliance State:

Gas Off
Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Turn Hot Water Tap On
DHW temperature control to maximum
CH temperature control to minimum
Connect the air pressure switch charge kit to +ve connection on the air pressure switch
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Measurement:

Note the operating pressure indicated on the pressure switch.
Allow fan to run for a few seconds then increase the pressure via the syringe to that indicated on the pressure switch.
Sparking should then be observed at the electrodes.
Note:
If continuity is not obtained it is permissible to increase the pressure by 50%.
100 Pascals = 1mbar / 50 Pascals = 0.5mbar