Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
DHW temperature control to maximum
CH temperature control to minimum
Loosen the outlet test point screw (P2) and attach U-gauge to the test point.
Set flow rate at tap to approximately 5 l/min
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow burner to fire and water to heat.
Does the burner pressure modulate as the water temperature is satisfied?
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.