Set Appliance State:
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
if required, reset boiler.
Run the appliance and allow the system to heat.
Monitor the boiler flow temperature.
Boiler flow temperature should reach approximately 85 - 88°C then maintain flow temperature or shut down without going to the fault code.
Note:
To speed up the process the heating load can be reduced by turning off some radiators.
Run the appliance and allow the system to heat.
Monitor the boiler flow temperature.
Boiler flow temperature should reach approximately 85 - 88°C then maintain flow temperature or shut down without going to the fault code.
Note:
To speed up the process the heating load can be reduced by turning off some radiators.