Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Attach U-gauge to gas inlet pressure test point
Ensure No demands
Ensure No demands
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
If required, reset boiler.
With a standing pressure registered on the U-gauge, turn off the inlet gas supply isolation valve.
Turn On a DHW tap & allow the ignition sequence to commence.
During the sparking phase of ignition the gas pressure registered on the U-gauge should be seen to drop away, indicating that the gas valve has opened. (see note 1.)
Note.
1.The boiler will enter lockout after 5 attempts of ignition, approximately 30 seconds between each attempt, repeat test from set state as required until test is complete.
2. When the test is complete checked for gas soundness.
With a standing pressure registered on the U-gauge, turn off the inlet gas supply isolation valve.
Turn On a DHW tap & allow the ignition sequence to commence.
During the sparking phase of ignition the gas pressure registered on the U-gauge should be seen to drop away, indicating that the gas valve has opened. (see note 1.)
Note.
1.The boiler will enter lockout after 5 attempts of ignition, approximately 30 seconds between each attempt, repeat test from set state as required until test is complete.
2. When the test is complete checked for gas soundness.