Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Draw back rubber shroud covering the flame sense electrode and lead
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Press Reset to cancel purge cycle countdown.
Ensure there is no demand.
Measure the voltage between the flame sense electrode and a suitable Earth.
Expected voltage approximately 91 VAC.
Ensure there is no demand.
Measure the voltage between the flame sense electrode and a suitable Earth.
Expected voltage approximately 91 VAC.

Isolate as per TOPs P4
and refit as necessary