Set Appliance State:
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
This fault code is displayed when boiler has gone
to a lockout fault code 5 times within a set time.
When this happens the boiler enters a safety mode and will not reset normally.
Turn the power off then on at the fused spur.
"RESET" should now be displayed on the top left of the screen and boiler can now be reset (hold RESET button for approx. 2 seconds), after resetting once it should display the previous code, then a further reset will be needed.
You may wish to access fault code history to see the 5 faults that caused E08.
1. Hold "INFO" button until display shows d1 (approx. 2 seconds).
2. Tap "INFO" button until display shows d9.
3. Rotate the CH temperature control knob to see last 5 faults.
To exit press the "RESET" button for approx. 2 seconds until display changes.
Please select an option below:
INVESTIGATE FAULT CODE SHOWN AFTER RESETTING E08 / FAULT HISTORY
UNABLE TO RESET E08 FAULT CODE
to a lockout fault code 5 times within a set time.
When this happens the boiler enters a safety mode and will not reset normally.
Turn the power off then on at the fused spur.
"RESET" should now be displayed on the top left of the screen and boiler can now be reset (hold RESET button for approx. 2 seconds), after resetting once it should display the previous code, then a further reset will be needed.
You may wish to access fault code history to see the 5 faults that caused E08.
1. Hold "INFO" button until display shows d1 (approx. 2 seconds).
2. Tap "INFO" button until display shows d9.
3. Rotate the CH temperature control knob to see last 5 faults.
To exit press the "RESET" button for approx. 2 seconds until display changes.
Please select an option below:
INVESTIGATE FAULT CODE SHOWN AFTER RESETTING E08 / FAULT HISTORY
UNABLE TO RESET E08 FAULT CODE