Set Appliance State:
Mains Power Off
CH Demand
Purge Switch in NORMAL position
HW Switch in OFF position
CH Switch in CH Continuous position
CH Potentiometer set to maximum
HW Switch in OFF position
CH Switch in CH Continuous position
CH Potentiometer set to maximum
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Allow the Fan to operate and the Pilot to ignite.
Measure the Voltage across the White wire and the Black wire on the Gas Valve Main Solenoid.
Measure the Voltage across the White wire and the Black wire on the Gas Valve Main Solenoid.

Isolate as per TOPs P4
and refit as necessary