Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach FGA temperature clamps to the primary heat exchangers flow and return pipe as indicated by the red arrows
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow CH to run for a few minutes.
Expect a differential temperature of approximately 20°C or less.
Is the differential as expected?
Note:
The differential measured on initial firing may be slightly higher.
Expect a differential temperature of approximately 20°C or less.
Is the differential as expected?
Note:
The differential measured on initial firing may be slightly higher.