Set Appliance State:
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow boiler to run and ignite for CH demand.
Boiler should run up to temperature (approx 82°C to 88°C flow temperature shown on display) and then shut down or modulate to maintain temperature.
Does the boiler operate as above or does overheat fault code reoccur?
Note:
To reduce time taken for this test you may wish to turn off some radiators.
Boiler should run up to temperature (approx 82°C to 88°C flow temperature shown on display) and then shut down or modulate to maintain temperature.
Does the boiler operate as above or does overheat fault code reoccur?
Note:
To reduce time taken for this test you may wish to turn off some radiators.