Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach temperature clamps to flow and return pipes as shown
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset appliance to skip self check and
allow boiler to run for DHW demand.
After 2 minutes the temperature differential
should be approx 25°C or less.
allow boiler to run for DHW demand.
After 2 minutes the temperature differential
should be approx 25°C or less.