Set Appliance State:
Mains Power Off
Ensure no demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset the appliance to ensure it is not in lockout.
Every time mains power is reinstated the appliance
should complete a self check of approx. 30 seconds.
During this the fan should run at a constant low speed then stop.
The pump should begin to run approx. 3 seconds after the
power is turned on and then run for a further 10 seconds.
Every time mains power is reinstated the appliance
should complete a self check of approx. 30 seconds.
During this the fan should run at a constant low speed then stop.
The pump should begin to run approx. 3 seconds after the
power is turned on and then run for a further 10 seconds.