Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to PCB (use Insulation Mat as required)
Remove white retaining clip, remove modulating
plug from the pump and make safe
Remove white retaining clip, remove modulating
plug from the pump and make safe
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the voltage between pin 7 (black wire) and
pin 9 (purple wire) on LV2.
Approx. 6V DC should be measured.
Note:
This test can be carried out during the appliance self check.
pin 9 (purple wire) on LV2.
Approx. 6V DC should be measured.
Note:
This test can be carried out during the appliance self check.

Isolate as per TOPs P4
and refit as necessary