Set Appliance State:

Ensure DHW temperature control is set to Max (60°C)
Ensure boiler is cool (to create demand for preheat)
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Switch preheat On, press ECO button (approximately 1 second) display should display Preheat.
Ensure any internal / external programmers with hot water function are calling for hot water.
Allow boiler to ignite and run for preheat.
Observe the flow temperature, at approximately 60 - 68°C flow temperature, the boiler should shut down, preheat complete.