Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap ON
DHW Temperature Control to MAX
Attach temperature clamps to flow and return pipes of the primary heat exchanger as illustrated
Note:
Depending on access and the type of temperature clamps you have you may need to use a temperature probe for the pipe leading to the pump assembly.
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow boiler to run for approximately 4 minutes.
Measure the temperature differential across flow and return.
Expect a differential of approximately 25°C or lower.