Set Appliance State:
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Access 2.1A in the parameter settings.
Click here for more information on accessing and setting boiler parameters.
Has the max CH output been set correctly for the system?
Default and maximum value is 24kW.
If adjustment is required it can be changed by altering one
or both menu 2 option 2.1A and menu 3 option 3.1A.
(2.1A cannot be set higher than 3.1A is set to).
Note:
Appliance will not display temperature setting during its self check.
Click here for more information on accessing and setting boiler parameters.
Has the max CH output been set correctly for the system?
Default and maximum value is 24kW.
If adjustment is required it can be changed by altering one
or both menu 2 option 2.1A and menu 3 option 3.1A.
(2.1A cannot be set higher than 3.1A is set to).
Note:
Appliance will not display temperature setting during its self check.