outside model, not currently used.

Observation:

Para No.ParameterDescriptionDefault Value
2.1A*Maximum Power CHRange rate of CH, adjustment in kW , max 24kW24kW
2.1CPump head selectionPump map(load and modulation percentage) 0 = Variable speed 1 to 4 option pump maps0
2.1EPump energy saving mode4 = mode ON 5 = mode OFF4
2.1HMin pump speed (speed at max CH burner load)Parameter only visible when 2.1C is set to 0 10%
2.1JMax pump speed(speed at max burner load)Parameter only visible when 2.1C is set to 0100%
2.2CAir purge modeThis feature can be selected to purge the system and boiler of air, 0 = off 1 = auto, active approx 100secs0
2.3BAnti cycle time for CHAmount of time between stop and starts of the main heat ex for CH, between 0 and 60 min10 min
2.3CAnti fast cycle temperature hysteresis Sets temperature drop before the burner restarts, in addition to "anti fast cycle time" between 2 to 15°K6°K
Note:
1°K=1°C