Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn hot water tap on with a flow rate of approximately 3 l/min
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure voltage across the white and black contacts of the flow turbine inline connector.
Voltages should be measured as in the range below.
Note:
Ensure good connections are made whilst carrying out this test.
Voltages should be measured as in the range below.
Note:
Ensure good connections are made whilst carrying out this test.