Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
Turn Hot Water Tap On
Remove the gas valve connectors from the gas valve.
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

On/Off switch On.
Allow boiler to commence its ignition sequence, measure voltage at both of the disconnected gas valve connectors.
Approximately 38 volts DC should be measured at both locations.
Notes:
1.There are two types of gas valve for this appliance but the test remains the same for either valve.
2.Take care not to short the connections.
3. If the boiler is in lockout it will need to be reset.
4. Ensure a good, firm contact is made with the gas valve lead connectors.