Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove the DC pump connector from the PCB and make safe
Remove vent screw from pump.
Remove vent screw from pump.
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Does the Pump now run?
Note:
Ensure any water released from the vent screw is safely contained and cannot come into contact with the boilers electrics.
Note:
Ensure any water released from the vent screw is safely contained and cannot come into contact with the boilers electrics.
Isolate as per TOPs P4
and refit as necessary