Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach pressure gauge to fan pressure test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Fan pressure should reach approximately -2.1 mbar or greater.
Notes:
1. The pressure measured will be negative.
2. When pressure gauge is removed pressure point cap should be replaced.
Notes:
1. The pressure measured will be negative.
2. When pressure gauge is removed pressure point cap should be replaced.
Isolate as per TOPs P4
and refit as necessary