Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
Attach temperature probes as indicated by the red arrows
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow burner to ignite and CH to operate and reach a reasonable
operating temperature, approximately 55°C.
Measure the temperature differential across the primary heat exchanger.
Expect approximately 11-20°C
Note:
To reduce the time for the test the heating load can be
reduced by turning off some radiators.