Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Unclip Diverter Valve head from the body and leave in a safe location
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Operate the appliance in service mode.
FOR INSTRUCTIONS ON SERVICE MODE CLICK HERE
Test 1
Run the appliance in Maximum output mode and carry out a performance test.
Test 2
Run the appliance in Minimum output mode and carry out a performance test.
Performance readings should be in accordance with manufacturers instructions.
Please select from one of the options below:
PERFORMANCE READINGS ON MAXIMUM AND MINIMUM SATISFACTORY
BURNER DROPS OUT WHEN IN MINIMUM OUTPUT MODE
PERFORMANCE READINGS OUT OF RANGE
Note: Refit diverter valve head to body after test.
FOR INSTRUCTIONS ON SERVICE MODE CLICK HERE
Test 1
Run the appliance in Maximum output mode and carry out a performance test.
Test 2
Run the appliance in Minimum output mode and carry out a performance test.
Performance readings should be in accordance with manufacturers instructions.
Please select from one of the options below:
PERFORMANCE READINGS ON MAXIMUM AND MINIMUM SATISFACTORY
BURNER DROPS OUT WHEN IN MINIMUM OUTPUT MODE
PERFORMANCE READINGS OUT OF RANGE
Note: Refit diverter valve head to body after test.