Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature probe to pipe as indicated by the red arrow.
Set boiler temperature control for CH to max
Set boiler temperature control for CH to max
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Run the appliance and allow the system to heat.
Note:
To speed up the process the heating load can be reduced by turning off some radiators. If overheat occurs Isolate Appliance Immediately.
Please choose from one of the options below:
BURNER SHUTS DOWN AT APPROXIMATELY 85°C
BOILER GOES TO OVERHEAT BEFORE 85°C
TEMPERATURE EXCEEDS 85°C AND CONTINUES TO HEAT
Note:
To speed up the process the heating load can be reduced by turning off some radiators. If overheat occurs Isolate Appliance Immediately.
Please choose from one of the options below:
BURNER SHUTS DOWN AT APPROXIMATELY 85°C
BOILER GOES TO OVERHEAT BEFORE 85°C
TEMPERATURE EXCEEDS 85°C AND CONTINUES TO HEAT