Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach temperature probes to the flow and return pipes as indicated by the red arrows
Run DHW tap at a flow rate of approximately 12 l/min
Attach a U gauge to burner pressure test point
Run DHW tap at a flow rate of approximately 12 l/min
Attach a U gauge to burner pressure test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow DHW to run for a couple of minutes.
Expect a temperature of approximately 20°C or less?
Also monitor the burner pressure, it should remain steady and not modulate down prematurely before the hot water temperature is reached.
Is the differential as expected?
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Expect a temperature of approximately 20°C or less?
Also monitor the burner pressure, it should remain steady and not modulate down prematurely before the hot water temperature is reached.
Is the differential as expected?
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Isolate as per TOPs P4
and refit as necessary