Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove the red leads from the pump proving microswitch
Remove the microswitch assembly from the boiler
Remove the microswitch assembly from the boiler
Measurement:
Test: 1
Measure the resistance across the microswitch
Expect open circuit.
Test 2:
Depress the micro switch with your finger to simulate the
flow switch spindle.
Measure the resistance across the microswitch
Expect continuity / zero resistance.
Measure the resistance across the microswitch
Expect open circuit.
Test 2:
Depress the micro switch with your finger to simulate the
flow switch spindle.
Measure the resistance across the microswitch
Expect continuity / zero resistance.

Isolate as per TOPs P4
and refit as necessary