Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to PCB (use Insulation Mat as required)
DHW Preheat selector to MAX position
Ensure appliance is cool
DHW Preheat selector to MAX position
Ensure appliance is cool
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure voltage between pins 5 and 7 at connector A2 on the PCB.
Is mains voltage present?
Note:
The mains voltage should be present for greater than 5 seconds, if the voltage is not present for at least 5 seconds then select the "mains voltage absent" outcome below.
Is mains voltage present?
Note:
The mains voltage should be present for greater than 5 seconds, if the voltage is not present for at least 5 seconds then select the "mains voltage absent" outcome below.

Isolate as per TOPs P4
and refit as necessary