Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach FGA temperature clamp to the flow pipe
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Cancel purge cycle & if required, reset boiler.
Run the appliance and allow the system to heat.
Monitor the boiler flow temperature.
Boiler flow temperature should reach approximately 75°C then maintain flow temperature or shut down without going to the A02 fault code.
Please choose from one of the options below:
Run the appliance and allow the system to heat.
Monitor the boiler flow temperature.
Boiler flow temperature should reach approximately 75°C then maintain flow temperature or shut down without going to the A02 fault code.
Please choose from one of the options below: