Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to detection electrode connection
Ensure No demands
Ensure No demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Cancel purge cycle & if required, reset boiler.
Measure for A/C voltage between the detection electrode connection and a suitable earth.
Expected voltage approximately 89 vac.
Measure for A/C voltage between the detection electrode connection and a suitable earth.
Expected voltage approximately 89 vac.

Isolate as per TOPs P4
and refit as necessary