Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect and remove ignition lead from heat exchanger / spark generator
Measurement:
Check spark electrode and lead is in good overall condition:
Ceramic uncracked
Spark gap between electrodes should be 3.5mm +/- 1mm
Lead not damaged or shorting
Measure the resistance from the tip of the electrode to the end of the lead.
(if needed clean tip of electrode to get a good connection)
Resistance should be approximately 1.2kΩ
Note:
Ensure all disturbed seals and washers
are in good condition on reassembly.
Refer to ADAPT for replacement advise.
Measure the resistance from the tip of the electrode to the end of the lead.
(if needed clean tip of electrode to get a good connection)
Resistance should be approximately 1.2kΩ
Note:
Ensure all disturbed seals and washers
are in good condition on reassembly.
Refer to ADAPT for replacement advise.

Isolate as per TOPs P4
and refit as necessary