Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Attach temperature probes to flow & return pipes at the bottom left of the combustion chamber
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Cancel purge cycle & if required, reset boiler.
Allow the burner to ignite and appliance to run for DHW.
With the appliance still running for DHW
measure the temperature differential.
Expect a differential of approximately 25°C or less.