Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect and remove rectification lead from heat exchanger
Measurement:
Check rectification electrode and lead is in good overall condition:
Ceramic uncracked
Electrode not warped or distorted
Lead not damaged or shorting
Measure the resistance from the tip of the
electrode to the end of the lead. (if needed
clean tip of electrode to get a good connection)
Resistance should be short circuit (zero resistance).
Note:
Ensure all disturbed seals and washers
are in good condition on reassembly.
Refer to ADAPT for replacement advise.
Measure the resistance from the tip of the
electrode to the end of the lead. (if needed
clean tip of electrode to get a good connection)
Resistance should be short circuit (zero resistance).
Note:
Ensure all disturbed seals and washers
are in good condition on reassembly.
Refer to ADAPT for replacement advise.

Isolate as per TOPs P4
and refit as necessary