Set Appliance State:
Mains Power Off
Selector switch to Hot Water position
DHW temperature control set to MAX
Preheat OFF
DHW temperature control set to MAX
Preheat OFF
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Ensure the start-up sequence has completed, the pump and fan have stopped and the boiler is showing 00.
Run the hot tap with a flow rate of 3 l/min.
A tap symbol should appear on the display (and change to showing temperature)
and then the fan and pump should run.
Does the boiler react as described above?
Run the hot tap with a flow rate of 3 l/min.
A tap symbol should appear on the display (and change to showing temperature)
and then the fan and pump should run.
Does the boiler react as described above?