Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Selector switch set to DHW/CH position
Temperature controls set to MAX
Preheat OFF
Temperature controls set to MAX
Preheat OFF
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Test 1. Apply a CH demand.
Inspect the diverter valve motor, does it move to the fully extended position during a heating demand?
Test 2. Turn a hot water tap ON.
Does the motor now move to the fully retracted position?
Note.
Location is behind the condensate trap, an inspection mirror may help with observation.
Inspect the diverter valve motor, does it move to the fully extended position during a heating demand?
Test 2. Turn a hot water tap ON.
Does the motor now move to the fully retracted position?
Note.
Location is behind the condensate trap, an inspection mirror may help with observation.